Magnetic flow meter installation guidelines

 
  Email:sales01@cxflowmeter.com
 
An electromagnetic flow meter is an instrument used to measure the flow of conductive liquids and slurries in closed pipes below 5 microsiemens (Siemens: unit of conductivity). Its performance is not affected by properties such as corrosiveness, viscosity, pressure, density, acidity and alkalinity of the medium. It can measure the flow of liquids, pastes, and slurries in water, wastewater, beverages, pharmaceuticals, fertilizers, dairy, food, paper, medical, petrochemical, chemical, mining and agriculture industries. It is also commonly used to measure steel plants and power plants. of cooling water flow.
 
2. Installation guidelines
 
1. The Magnetic flow meter must be installed in a location free of interfering components (valves, T-tubes, elbows, pumps, etc.). To ensure there is no turbulent laminar flow upstream of the electromagnetic flowmeter. Therefore, the electromagnetic flowmeter must be installed in a straight pipe at a distance of at least 3xDN from upstream interfering components and at least 2xDN from downstream interfering components.
 
IMPORTANT: If there is a valve in the pipeline, the electromagnetic flowmeter should always be installed on the downstream side of the valve
 
2. If reducing joints are required, the internal angle shall not exceed 7.5°. The minimum length to keep the angle below 7.5° can be calculated by the following formula:
 
L = (D - d) x 7.63
 
Among them, "D" is the major diameter of the reducing joint, and "d" is the minor diameter of the reducing joint.
 
For example: If an electromagnetic flowmeter with a pipe diameter of DN80 is installed downstream of a 100mm pipe, the length of the reducing joint must be at least 152.6mm to keep the internal angle below 7.5°.
 
3. The flange connection of the electromagnetic flowmeter must be assembled concentrically on the upstream and downstream sides; if the connection is improper, it will cause liquid turbulence, thus affecting the measurement accuracy.
 
NOTE: The washer and ground ring must also be installed concentrically.
 
4. The mag flow meter must maintain a full pipe state. Therefore, the electromagnetic flowmeter is strictly prohibited from being installed at the highest point or free outlet in the pipeline system. Due to the influence of gravity, the pipe may be empty or not full.
 
 
5. If the liquid being measured carries particles, such as when measuring sludge, sewage, etc., the electromagnetic flowmeter must be installed vertically and keep the flow direction from bottom to top to ensure that the electromagnetic flowmeter is always full of pipes and can effectively reduce the occurrence of bubbles. .

 


If you want to know about electromagnetic flow meter selection, quotation and installation, please feel free to consult CIXIFM winny:
 
  Email:sales01@cxflowmeter.com




 

Last:magnetic flow meter vs turbine .. Next:How to choose the model of ultr..

Contact Us

Office Address: Room 402, No. 650, Xinzhuan Rd., Jiuting Town, Songjiang District, Shanghai, China (Mainland)

Phone:021-57635022

E-mail:info@gnflowmeter.com

E-mail:sales@gninstruments.com

關(guān)閉
粉粉嫩嫩的18虎白女,国产在线高清伦免费理视频,一本久久a久久精品vr综合,国产线播放免费人成视频播放,国产在线精品91国自产拍免费