Type:CX-PT-3051 single flange pressure transmitter

Illustrate: Single flange pressure transmitter is widely used for measuring differential pressure (or pressure), level, density of liquid, gas or steam and convert the value of above into current signal output or digital protocol output.

CX-PT-3051 Single Flange Pressure Transmitter
 

 

Brief Introduction
  1. Widely used for measuring differential pressure (or pressure), level, density of liquid, gas or steam and convert the value of above into current signal output or digital protocol output.
  2. The pressures are directly applied to the isolating diaphragm that provide isolation and resistance against process fluid corrosion.
  3. Being microprocessor based, the electronic circuit is extremely versatile and accurate.
  4. Combined with the sensor precision, it provides the high accuracy and range ability.
  5. Transmitter performance is improved by continuous monitoring of the sensor temperature and corresponding corrections.
  6. A local display permits easy reading and writing of data.
Dimension


 
Main Parameters


Medium liquid, gas and steam
Measuring Range  0~0.1kPa to 0~40MPa
Output 4~20mA DC+HART protocol
Accuracy ±0.1%FS
Range and null point Adjustable
Power Supply 12~45V DC, generally 24V DC
Protection  IP65
Storage Temperature -40℃~+125℃
Overload Limit 150%-200% ofrated range
Load Resistance ≯750Ω(See below diagram 1 for load characteristic )
Relative Humidity 5~95%
Converter housing Low copper cast aluminum alloy with Polyurethane paint
Fill Fluid Silicon / Fluorine Oil 
Process Connections 1/2NPT, 1/4NPT
Static pressure 4, 10, 25, 32Mpa
Mounting Directly supported by piping or optionally with mounting bracket for 2" pipes or with direct or remote seals. 3-way valve
Maximum positive shift 500% of minimum adjusting span
maximum negative shift 600% of minimum adjusting span
Material Flange/Adaptor Stainless Steel 316/Monel/ Haste alloy/Carton Steel
Drains/Vents Stainless Steel 316/Monel / Haste alloy
Diagrams Stainless Steel 316/Monel /Haste alloy C/ Tantalum
Wetted O-Ring Viton/ Buna-N
Seal O-Ring Viton/ Buna-N
Bolts & Nuts Carton Steel/Stainless Steel316
 
Wiring Diagrams

Connect the bench equipment as shown in Figure, and turn on the HART-based communicator by pressing the ON/OFF key. The communicator will search for a HART-compatible device and will indicate when the connection is made. If the communicator fails to connect, it will indicate that no device was found.



Last:CX-PT-3051L flange level transm.. Next:CX-PT-530 differential prssure ..

Contact Us

Office Address: Room 402, No. 650, Xinzhuan Rd., Jiuting Town, Songjiang District, Shanghai, China (Mainland)

Phone:021-57635022

E-mail:info@gnflowmeter.com

E-mail:sales@gninstruments.com

關(guān)閉
粉粉嫩嫩的18虎白女,国产在线高清伦免费理视频,一本久久a久久精品vr综合,国产线播放免费人成视频播放,国产在线精品91国自产拍免费